ARGYNET LABSolutionsStrengthening with carbon fibre: when, where and how — flexure, shear and confinement
Back to Solutions
Ενίσχυση με ανθρακονήματα: πότε, πού και πώς — κάμψη, διάτμηση και περίσφιγξη

Strengthening with carbon fibre: when, where and how — flexure, shear and confinement

Last updated:

Solutions & Applications · Concrete Repair & Structural Strengthening

Carbon fibre does not repair concrete — it adds tension where tension is missing. A fabric less than a third of a millimetre thick, bonded in the right place with the fibres in the right direction, does the work of additional reinforcement without changing the member's section, weight or space.

When strengthening is needed

Strengthening with fibre-reinforced polymers (FRP) is always decided by a structural design. The reasons that bring it to the table are few and recurring:

ReasonWhat has changed in the member
Change of use · higher imposed loadsA home that becomes an office or shop, new equipment, a green roof, an added storey — loads exceed those of the original design
Loss of reinforcement sectionCorrosion that has eaten part of the steel — repair restores the geometry, not the load-bearing capacity
Design or construction errorsToo little or misplaced reinforcement, bars cut for service penetrations, new openings in slabs
Seismic upgradingAn assessment to the Greek retrofit code (KAN.EPE) that shows a shortfall in shear or ductility
Restoration after damageEarthquake, vehicle impact or fire

Three mechanisms, three ways of installing

FRP works only in the direction of its fibres. So the first question is not "which material" but which force is missing:

StrengtheningWhere it goesFibre directionSystem
Flexure · beams, slabs, cantileversIn the tension zone — the soffit at midspan, the top face over supports and on cantileversAlong the spanS&P C-Laminate with SINMAST P 103 · or C-Sheet 240 with S2W & S2 WV
Shear · beams, T-beamsOn the beam sides, as strips or continuous fabric in a U-wrap or full wrapTransverse to the beam axisS&P C-Sheet 240 or 640 with S2W & S2 WV
Confinement · columnsClosed wrap over the full height or in zonesAround the perimeterS&P C-Sheet 240 with S2W & S2 WV

Confinement is the most "efficient" use of fabric: the closed wrap restrains the core concrete as it tends to expand, increasing the column's axial capacity and above all its ductility — exactly what seismic upgrading asks for.

Fabric or laminate?

S&P C-Sheet · fabricS&P C-Laminate · laminate
FormFlexible unidirectional fabric, impregnated on sitePrefabricated rigid laminate in an epoxy matrix (pultrusion)
TypesC-Sheet 240: 230, 330, 430 g/m² (dry method) and 630 g/m² (wet) · C-Sheet 640: 430 g/m²SM 150/2000 and HM 200/2000 · widths 50–150 mm · thicknesses 1.2, 1.4 and 2.8 mm
Modulus of elasticity≥ 240–265 GPa (240) · ≥ 640 GPa (640)≥ 170 GPa (SM) · ≥ 205 GPa (HM)
ForceUp to 1,420 kN per metre width (maximum, C-Sheet 240 · 630 g/m²)Design force up to 470 kN (SM) and 554 kN (HM) per 120/2.8 laminate
GeometryFollows corners and curves — the only option for confinement and shearFlat surfaces only, with strict flatness
Main useConfinement, shear, flexure · C-Sheet 640: shear and anchoring laminate endsFlexural strengthening of beams, slabs and cantilevers
ResinsSINMAST S2W (primer) + SINMAST S2 WV (impregnation and bonding)SINMAST P 103 (epoxy paste) · Cleaner X3

On a long-span slab, laminates deliver a lot of force in a few strips and go on quickly. On a beam that needs both flexure and shear, the two are usually combined: laminates on the soffit and C-Sheet U-strips on the sides, which also anchor the laminate ends.

ARGYNET Note

FRP does not bond "to the concrete" — it bonds to the first few millimetres of its surface. Carbon fibre is several times stronger than steel, yet the strengthening almost always fails the same way: it debonds, taking a thin layer of concrete with it. That is why the pull-off strength of the substrate is the figure that decides the job — not the strength of the fibre.

A second point: FRP is passive reinforcement. It only carries the loads added after it is installed. The more the member is unloaded or propped during installation, the more the strengthening contributes — this is set by the design.

At ARGYNET we provide the design team with the technical data sheets, declarations of performance and design values for each type, and calculate quantities of fabric, laminates and resins per member.

The substrate decides the strengthening

Each material in the system declares its own requirements. On site, the strictest one applies:

RequirementValueApplies to
Concrete age≥ 21–28 daysC-Sheet · C-Laminate
Pull-off strength≥ 1.0 N/mm² (fabric) · ≥ 1.2 N/mm² (S2W) · ≥ 1.5 N/mm² (P 103) · 2.0 N/mm², minimum 1.5 (laminates)Per system
Substrate moisture≤ 4 %All
Flatness≤ 5 mm over 2 m and ≤ 1 mm over 0.3 mC-Laminate
Edge roundingRadius > 25 mmC-Sheet in confinement and shear
Repairs beneath the FRPStructural mortar with modulus of elasticity ≥ 19 GPa (SINTOCRETE R4) · cured ≥ 7 days before the resinsAll
CleanlinessNo laitance, loose material, dust, oil or old paint — mechanical preparationAll

If the concrete has corroding reinforcement, the order is strict: stop the corrosion first, then strengthen the member. Fabric over active corrosion seals the problem in — and debonding follows together with the unsound substrate. The repair procedure is described in detail in the solution on rusted reinforcement.

Installing C-Sheet fabric

  1. Preparation: mechanical removal of laitance and loose material, edge rounding, repairs with SINTOCRETE (R4), dust removal.
  2. SINMAST S2W primer: one coat, about 0.300 kg/m², with a short-pile roller or rubber squeegee, without puddles. Wait 25 minutes (summer) to 60 minutes (winter).
  3. SINMAST S2 WV resin: about 0.250–0.450 kg/m² per fabric layer. For soffits and heavy fabrics, viscosity is adjusted with Thixo-Factor.
  4. Placing the fabric: pressed with a roller in the fibre direction, so it is fully impregnated and air is expelled. Overlap ≥ 150 mm in the fibre direction — never on or near an edge.
  5. Multiple layers: wet on wet, with resin on every layer.
  6. Sealing: a final coat of S2 WV, about 0.150–0.250 kg/m², broadcast with quartz sand if render follows.

Installing C-Laminate

  1. Cutting and cleaning: the laminate is cut with a grinder and cleaned with Cleaner X3, waiting more than 5 minutes.
  2. SINMAST P 103 paste: about 1 mm on the member and about 2 mm on the laminate, in a prism shape along the axis. Consumption about 260–300, 520–700 and 630–800 g per linear metre for 50, 100 and 120 mm laminates.
  3. Placing: within 1 hour of application (1.5 hours if both surfaces are coated). Pressed with a hard rubber roller, excess removed.
  4. Anchoring the ends: S&P C-Sheet 640 strips placed transversely at the ends, in the critical zone. The laminate end is where debonding begins.

Site conditions

  • Temperature: +10 to +35 °C for the system (fabrics and laminates are declared from +8 °C, the resins from +10 °C).
  • Dew point: substrate at least 3 °C above it · relative humidity ≤ 65 %. Condensation on the surface defeats adhesion.
  • Protection: from rain for 12 hours after applying the resins · full cure of P 103 in 15 hours.
  • Crew: specialised, with quality control per member — pull-off tests before, tap testing for voids after.

Temperature and fire

The weak point of the system is not the fibre but the epoxy resin. SINMAST P 103 declares a glass transition temperature of 73 °C: above it the adhesive softens and force transfer to the fibre is lost. This has two consequences:

  • In the design: in a fire scenario the strengthening is usually considered lost, and the unstrengthened member is checked for the loads of the accidental situation.
  • In construction: where fire resistance is required, the FRP is protected. The fabrics accept render, paint or a fire-protective coating.

Laminates and fabrics on members exposed to the sun, such as cantilevers and external beams, are also protected from UV by the final finish.

What the design needs

  • Survey and diagnosis: reinforcement, concrete strength (cores), carbonation, damage, pull-off tests.
  • Design values per material: modulus of elasticity, design thickness (0.113–0.333 mm for C-Sheet), design strain (ε 0.6 / 0.4 % for C-Sheet 240 · 6 / 8 ‰ for C-Laminate) and the manufacturer's safety factor (1.2 for hand lay-up).
  • Resin certification: SINMAST S2 WV and SINMAST P 103 CE-marked to EN 1504-4 (structural bonding).
  • Details: anchorage lengths, end anchorages, overlaps, corner radii, protection.
  • Quality control plan: substrate tests, record of application conditions, void checks.

Mistakes that cost

MistakeConsequence
FRP without a structural designThe material goes in the wrong place or direction and adds nothing — or moves the failure elsewhere
Fabric over a sharp edgeStress concentration and fibre rupture at the corner long before the design strength
Fabric overlap on an edgeThe joint opens at the most highly stressed point
Laminates on an uneven surfaceVoids beneath the laminate and local debonding
Laminate ends without anchorageDebonding starts at the end and "peels" the laminate
Ordinary mortar repairs beneath FRPLow modulus — the repair deforms and the strengthening does not work
Application in damp conditions or near the dew pointThe resin does not bond · white blooming and debonding
Unprotected FRP where fire resistance is requiredThe strengthening is lost in the first minutes of a fire

Sequence of works

  1. Survey and diagnosis of the structure and the concrete.
  2. Structural design of the strengthening: mechanism, material, quantities, details.
  3. Unloading or propping of the member, as set by the design.
  4. Concrete repair with reinforcement corrosion protection and SINTOCRETE (R4) — cured ≥ 7 days.
  5. Surface preparation and pull-off tests.
  6. FRP installation with a record of temperature, humidity and dew point.
  7. Void checks and final protection: render, paint or fire protection.

FRP Strengthening System

Substrate Preparation