Rusted reinforcement in concrete? Why does concrete crack and how can corrosion be stopped?
Last updated:
Rust expands and causes the coating to crack. Anti-corrosion treatment for the reinforcement, R3/R4 repair compound and surface protection to prevent further cr
The system at a glance
- SINTOCRETE AntiCorr ST | Corrosion inhibitor
- SINTOCRETE | Fibre-reinforced Repair Mortar | R4
- SINTOCRETE Basic | Fibre-reinforced Repair Mortar | R3
- SINTOPLAST | LATEX synthetic resin
- SINTOMIX SM N | Mass waterproofing compound
- VANDEX CEMELAST 100 | Two-component elasticised waterproofing mortar
- VANDEX BB 75 | 1C Cementitious Waterproofing Render
- CERESIT CR 166 Flexible 2-K | Flexible cementitious waterproofing compound
- S&P C-Sheet 240 | High-strength carbon fibre fabric
- SINMAST S2 WV | Epoxy resin for FRP fabrics
- SINMAST P 103 | Epoxy repair paste
- MuCis ad 19/ L | Diffusing retarder
- TECNOS 95 | Concrete superplasticiser
Solutions & Applications · Concrete Repair
Rust takes up many times the volume of the steel it corrodes. Inside the concrete, it has nowhere to go, so it pushes against the covering until it cracks and detaches it. That is why exposed, rusted reinforcement is not an aesthetic problem but a symptom — and that is why a simple cement mortar applied over the rust will flake off again within a few years. A lasting repair first stops the corrosion and then restores the cross-section.
Why does concrete crack?
Fresh concrete is highly alkaline, and in this environment the steel is covered by a thin protective film. As long as this film remains, the reinforcement does not rust. Two mechanisms cause it to deteriorate:
| Mechanism | What’s happening? | Where can we find him? |
|---|---|---|
| Carbonation | CO₂ in the air penetrates through the surface and gradually reduces the alkalinity. When the front reaches the reinforcement, the protection is lost | Slight overlap, porous concrete, old buildings, piles, balconies |
| Chlorides | Chloride ions penetrate the film even in alkaline concrete and cause localised, deep corrosion | Coastal buildings, salt, swimming pools, reservoirs |
With water and oxygen, corrosion progresses, and the expanding rust paves the way for even more water. It is a cycle that accelerates.
The symbols, in the order in which they appear
| Mark | What does this mean? |
|---|---|
| Brown rust spots on the surface | Corrosion has already begun and the products are corroding from the inside out |
| Cracks running parallel to the reinforcement | Rust has started to push through the coating |
| A ‘hollow’ sound when tapped, flaking | The covering has come away — it is going to fall off |
| Exposed reinforcement, thinner than the original | The cross-section is missing; verification by a structural engineer is essential |
Why a simple patch job fails
When a patch is applied with cement mortar over rust, three things remain as they were: the rust continues beneath the patch, the ordinary mortar shrinks and detaches from the old concrete, and the surrounding concrete remains carbonated. Often, the corrosion simply shifts to the edges of the patch and spalling reappears alongside it.
A repair that lasts: step by step
- Delimitation. Check for hollow areas using a hammer and mark the repair area slightly beyond the visible problem.
- Demolition. Removal of all loose concrete, including that behind the reinforcement bars, so that the reinforcement is exposed along its entire perimeter within the corroded zone.
- Cleaning of reinforcement. Removal of rust down to bare metal. If the cross-section has been significantly reduced, the engineer shall decide on additional reinforcement before work continues.
- Corrosion protection. Apply SINTOCRETE AntiCorr ST to the reinforcement (~0.14 kg per metre of Ø14 bar). The same material is also applied to the concrete as a bonding layer (≥ 0.5 kg/m²), inhibiting corrosion and restoring alkalinity in the zone.
- Wetting. The substrate must be thoroughly wetted prior to application of the repair compound.
- Cross-section repair. Fibre-reinforced thixotropic mortar in accordance with EN 1504-3: SINTOCRETE (R4, ~2 kg/m²/mm) or SINTOCRETE Basic (R3, ~17 kg/m²/cm). These may also be applied to vertical surfaces and beneath beams without formwork.
- Wet curing. 6–24 hours for R3, 24–48 hours for R4 — longer in hot and dry conditions.
- Surface protection. A flexible cementitious compound that delays carbonation throughout the entire element, not just at the repair site: Ceresit CR 166 or VANDEX CEMELAST 100 (sD for CO₂ greater than 50 m).
R3 or R4?
| SINTOCRETE Basic · R3 | SINTOCRETE · R4 | |
|---|---|---|
| Class EN 1504-3 | R3 | R4 — the highest |
| Typical use | Repairs due to corrosion in beams, columns, cantilevers and masonry | Structural repairs to load-bearing elements, coastal zone, industrial environment |
| Special features | Dimensionally stable, non-shrinking | Compensated for shrinkage, impermeable even under pressure, resistance to sulphates |
| Consumption | ~17 kg/m² per cm | ~2 kg/m² per mm |
| Wet maintenance | 6–24 hours | 24–48 hours |
When repair is not enough: reinforcement
If the reinforcement has lost a significant portion of its cross-section, restoring the geometry does not restore the load-bearing capacity. In such cases, following a structural analysis, the member is reinforced with FRP composite materials:
- S&P C-Sheet 240 — carbon fibre fabric for column wrapping and beam reinforcement, with epoxy impregnation resin SINMAST S2 WV.
- S&P C-Laminate — carbon fibre sheets for flexural reinforcement, bonded with epoxy paste SINMAST P 103.
The reinforcement is applied to concrete that has already been properly repaired: first, the corrosion is halted, then the element is reinforced.
Prevention in fresh concrete
The cheapest repair is the one that isn’t needed. In fresh concrete, corrosion is prevented by adequate cover, good compaction and admixtures: TECNOS 95 for a lower water-to-cement ratio, SINTOMIX SM N for a watertight mass and, in a coastal environment, MuCis ad 19/L — an inhibitor that diffuses through the porous structure to the reinforcement and remains effective even in the presence of chlorides.
Exposed reinforcement in a column or beam is not a job for a ‘handyman’. Before carrying out any removal work on a load-bearing element, the engineer must assess the damage: how much cross-section has been lost, whether shoring is required during the work, and whether reinforcement is necessary.
Repairs do not end with the mortar. Without corrosion protection for the reinforcement and without surface protection, the same process begins again — usually at the edges of the repair.
At ARGYNET, we specify the repair system on a component-by-component and environment-by-environment basis, and calculate quantities per m² and per thickness.
Mistakes that cost
| Incorrect | Consistency |
|---|---|
| Cement screed over slag | Corrosion continues from below; the patch is falling off again |
| Demolition only in front of the bar | The rear side of the reinforcement remains rusted and unprotected |
| Reinforcement without anti-corrosion treatment | The new mortar contains an active source of corrosion within it |
| Repair compound for dry substrates | Old concrete ‘absorbs’ the water from the mortar: poor adhesion, cracks |
| No wet maintenance required | Shrinkage cracks in repairs |
| Repair without surface protection | Carbonation progresses through the remainder of the element and corrosion appears alongside it |
Repair of Reinforcement & Concrete
Surface Protection
FRP Structural Reinforcement
Prevention in New Concrete
Related Solutions from ARGYNET LAB
Please send us photographs of the damage — we will draw up the repair specifications.
Request a Technical Quotation