How to insulate my roof
Roof & pitched tiled roof

How do I insulate my roof?

Last updated:

Mineral wool is the easy bit. The two sheets surrounding it and their arrangement determine whether the roof will rot from the inside.

The system at a glance

Solutions & Applications · Roof Insulation

The mineral wool between the joists is the easy part. The tricky bit is the two sheets surrounding it — one underneath and one on top — and their order. A roof with perfectly installed insulation but without a vapour barrier gets wet from the inside, loses its thermal value within two winters and causes the timber to rot.

The sequence of layers

From the heated space outwards:

LayerRoleKey point
Internal claddingFinish — plasterboard or timberIt is not airtight in its own right
Vapour barrierPrevents water vapour from inside the house from entering the insulationAlways on the warm side — beneath the insulation
Thermal insulationThermal insulation, sound insulation, fire protectionFilling without voids and without compaction
Vapour-permeable membraneKeeps out rain, allows water vapour to escapeAlways on the cold side — above the insulation
Ventilated cavityWicks away moisture and heatEntrance at Markiza, exit at Korfia
CoverTiles or other roofing materials—
ARGYNET Note

Without a vapour barrier, the insulation becomes damp from the inside. A family of four produces several kilograms of water vapour every day from breathing, cooking, bathing and drying clothes. Water vapour moves upwards and towards cooler areas. If it encounters no barrier, it passes through the plasterboard and condenses within the mineral wool, where the temperature falls below the dew point.

The result is not immediately apparent. The mineral wool gradually becomes saturated with moisture, loses its thermal insulation properties, and the moisture is transferred to the timber of the framework. By the time a stain appears on the ceiling, the damage has already been present for years.

There is only one rule, and there are no exceptions: the barrier must be on the warm side, and vapour must be allowed to escape on the cold side. Reversing this order traps moisture and is worse than having no membranes at all.

At ARGYNET, we specify the entire stratification and calculate materials per m².

Air-tightness is not just about windows

The vapour barrier also fulfils a second function: it acts as the airtight layer of the roof. Furthermore, the transport of moisture via air currents through a gap is many times greater than diffusion through a material. A gap of just a few millimetres allows more moisture to pass through than dozens of square metres of intact surface.

That is why continuity is key:

  • Overlaps sealed with tape, not simply overlapping.
  • Around the perimeter of roof windows using self-adhesive tapes — the point that every guide correctly mentions, but not the only one.
  • Penetrations: flues, pipework, cabling, light fittings — every hole must be sealed.
  • Connections with masonry at the perimeter and on the facades.

The two membranes are a pair, not alternatives

This is the most common source of confusion when ordering materials, and the two products are at opposite ends of the same spectrum:

FIBRANskin BARRIER 2400ESHADACH
PositionBeneath the insulation — warm sideAbove the insulation — cold side
RoleVapour barrier & airtight layerKeeps out rain and dust, whilst allowing water vapour to escape
Diffusion resistance Sd2400 m — practically impermeable0.02 m — effectively free vapour transmission

The difference is five orders of magnitude, and that is precisely what makes the system work: water vapour is prevented from entering from the inside, and any that does enter finds a free path to escape outwards. Reversed installation traps moisture inside the insulation.

ESHADACH: the loads are a measure of strength, not vapour permeability

All four versions have the same Sd = 0.02 m. What varies is the durability on site and during the first few years:

  • 95 g/m² — simple roofs with continuous boarding, in a sheltered location.
  • 150 g/m² — the balanced choice for a standard home.
  • 170 g/m² — the documented version with a public DoP; the safe choice when a design is in place.
  • 220 g/m² — exposed locations and roofs without a continuous substrate.

The actual failure mechanism is not vapour permeation but tearing: the membrane is punctured by the fixing nail and the wind enlarges the hole with every gust until it opens up. This is why tear resistance of 190/230 N, elongation of 55/80 per cent — which allows the membrane to stretch rather than tear when the timber moves — and the retention of 88 per cent of tensile strength after ageing.

Practical information: installation directly onto thermal insulation is expressly permitted under the DoP, as is use on roofs without a continuous screed. This is one of the few instances where the certificate covers the method and not just the material.

Which vapour barrier on the warm side?

BARRIER 2400 is the choice for new builds under controlled conditions. However, it is not the only option, and in two cases it is not the best:

Case studyMembraneWhy
New buildFIBRANskin BARRIER 2400 · Sd 2400 mComplete barrier, provided the substrate is dry and known
RenovationFIBRANskin SMART · Sd 8–18 m variableExisting timber may contain moisture; the membrane ‘opens up’ in the summer, allowing it to dry out
High humidity — bathrooms and kitchens beneath the loftFIBRANskin BARRIER 23 · Sd 29 mThe space generates moisture on a daily basis; virtually airtight, 25-year guarantee

A habitable loft under the sun

When the loft is inhabited directly beneath the roof tiles, particularly on a south or south-west facing side, the problem in summer is the radiation emitted by the heated roof tiles. This is where FIBRANskin VENT SILVER comes in, replacing a simple breathable membrane: a reflective coating with an emissivity of 0.10, a thermal resistance of up to 0.57 m²K/W in a vacuum according to EN ISO 6946, and an Sd value of 0.03 m — reflectivity does not compromise breathability. The reflective facing requires the ventilated cavity in front of it to function.

A comprehensive comparison of membranes, including all prices, can be found in the ‘Thermal Insulation and Waterproofing of Pitched Tiled Roofs’ solution.

The thermal bridge that isn’t taken into account

Timber trusses are not insulating. The thermal conductivity of timber is approximately four times that of mineral wool. At a typical beam spacing, timber occupies a significant proportion of the surface area — and each beam acts as a linear thermal bridge along its entire length.

Insulation applied only between the joists leaves these lines uncovered. The solution is a second layer beneath the joists, laid crosswise on an independent framework of metal profiles:

  • It covers the beams and eliminates the linear thermal bridge.
  • It creates an installation zone beneath the vapour barrier — that is, the wiring does not penetrate it.
  • It improves sound insulation against the sound of rain on roof tiles, which is not negligible in a habitable loft.

The second point is the most overlooked: every socket, switch and spotlight that passes through the vapour barrier is a permanent air leak. The services duct keeps them all on the inside.

Rolls or sheets

Roller shuttersSlabs
AdvantageSpeed in large, continuous formwork sections with a fixed pitchCutting accuracy, stability on an inclined surface
InabilityThey tend to sag on steep slopesMore cuts at irregular intervals
Typical useHorizontal loft slab, standardised timber-framed roofsSloping formwork, second cross-layer

In any case, mineral wool is a non-combustible material — in a timber roof, this is not a secondary characteristic but an essential contribution to the fire protection of the load-bearing structure.

Five installation rules

  1. Cut to size with an oversize of 1–2 cm: the material is fitted by rubbing it into the opening, leaving no gaps at the edges. A gap of one centimetre along the entire length of a beam acts as an air passage.
  2. Without compression: compressed mineral wool loses the trapped air, which is precisely what makes it insulating. The thickness must correspond to the available depth.
  3. Joint displacement between the two layers — a continuous joint running through the entire thickness constitutes a linear thermal bridge.
  4. Without filling the cavity: the insulation does not extend as far as the vapour barrier if a cavity is provided. At the eaves, the air inlet remains unobstructed.
  5. Temporary walkways during works — and personal protective equipment when handling materials.

Design series

  1. Will the loft be used as living space? If not, the insulation is installed in the horizontal slab and the roof remains cold and ventilated — a simpler and cheaper solution.
  2. Available truss depth: determines the thickness and whether a second layer is required.
  3. Required U-value for the climate zone, taking into account the thermal bridge of the beams.
  4. Membrane type: vapour barrier on the warm side, breathable on the cold side — and confirmation of suitability for pitched roofs.
  5. Services zone: if there are any cables and light fittings, these must be planned prior to the membrane design.
  6. Ventilation: inlet at the eaves and outlet at the ridge, with protection against birds and insects.

Roof Thermal Insulation

Roofing Membranes

Interior Cladding & Frame

Related Solutions from ARGYNET LAB

Is there a vapour barrier beneath your insulation — and is it continuous?